Skip to main content

Table 3 Distance relay settings

From: Protection and control of microgrids using dynamic state estimation

Function

Settings

Line and Ground Distance, Zone 1

0.0681  9.10° Ω, 1 cycle delay, compensation factor k = 2.959  78.63°

Line and Ground Distance, Zone 2

0.1065  9.10° Ω,0.15sdelay, compensation factor k = 2.959  78.63°

Line and Ground Distance, Zone 3

0.2214  9.10° Ω,0.5sdelay, compensation factor k = 2.959  78.63°