From: Protection and control of microgrids using dynamic state estimation
Parameter | Value |
---|---|
Series resistance matrix (per feet) | \( \left[\begin{array}{cccc}0.2649& 0.0101& 0.0101& 0.0101\\ {}0.0101& 0.2649& 0.0101& 0.0101\\ {}0.0101& 0.0101& 0.2649& 0.0101\\ {}0.0101& 0.0101& 0.0101& 0.2649\end{array}\right]m\Omega / ft \) |
Series reactance matrix (per feet) | \( \left[\begin{array}{cccc}0.7830& 0.6817& 0.6606& 0.6817\\ {}0.6817& 0.7830& 0.6817& 0.6606\\ {}0.6606& 0.6817& 0.7830& 0.6817\\ {}0.6817& 0.6606& 0.6817& 0.7830\end{array}\right]\mu H/ ft \) |
Shunt capacitance matrix (per feet) | \( \left[\begin{array}{cccc}0.1431& 0& 0& 0\\ {}0& 0.1431& 0& 0\\ {}0& 0& 0.1431& 0\\ {}0& 0& 0& 0.1431\end{array}\right] nF/ ft \) |