Skip to main content

Table 6 Case study 1: Actual vs. estimated zero-sequence line impedance

From: Relay performance verification using fault event records

Event

Zero-sequence line Impedance (Ω)

Error

 

Carson’s equation

Estimated

Magnitude

Phase angle

   

(%)

(degrees)

4

19.72+j56.22

24.06+j55.03

0.79

4.29

3

 

23.60+j54.30

0.63

4.16

2

 

21.84+j56.75

2.05

1.72

1

 

26.12+j57.37

5.79

5.15