Table 8 Performance of distance relay RA with PAZSD methodology for different faults with FR = 1.7 Ω at different distances

From: PMU based adaptive zone settings of distance relays for protection of multi-terminal transmission lines

Fault Condition

Impedance seen by the relay RA

Current Coefficients

New Zone Setting of

Performance of RA with proposed methodology

K 1

K 2

K 3

Zone 1

Zone 2

Zone of fault detection is?

Is detected zone correct? (Y/N)

LL Fault at 50 km

4.496  47.980

1.2813

1.2578

1.7422

40.58460.36°

76.09560.36°

Zone 1

Y

LLG Fault at 50 km

3.895  59.410

1.5547

1.3125

1.2969

36.21660.36°

67.90660.36°

Zone 1

Y

LG Fault at 150 km

14.445  53.480

2.6328

1.7969

2.2969

61.33060.36°

114.99460.36°

Zone 1

Y

LL Fault at 150 km

11.114  54.070

2.7891

2.6406

2.0625

64.97160.36°

121.82160.36°

Zone 1

Y

LL Fault at 250 km

31.75   − 275.120

4.3359

5.1324

2.0313

119.55860.36°

224.19160.36°

Zone 1

Y

LLG Fault at 250 km

32.444  51.750

3.9063

2.0938

5.4219

126.30260.36°

236.81660.36°

Zone 1

Y

LLG Fault at 300 km

53.717  87.030

2.2109

4.6016

5.1328

119.56760.36°

224.18860.36°

Zone 1

Y

LLL Fault at 300 km

50.457  79.350

3.7734

2.2344

4.7109

109.73960.36°

205.76160.36°

Zone 1

Y

LLG Fault at 350 km

81.044  61.890

2.7031

5.4375

5.3359

126.66560.36°

237.49760.36°

Zone 2

Y

LLL Fault at 350 km

76.823  76.770

4.6797

5.1719

5.4922

127.93960.36°

239.88660.36°

Zone 2