Table 2 Verification of Fault Analysis algorithm for AB fault in Three-Bus System

From: Robust fault analysis in transmission lines using Synchrophasor measurements

Fault Detection

 Fault Created

V1 (kV)

V2 (kV)

V3 (kV)

Are all of (V1-, V2-, V3) > 0 (or) IMax+ > τB (Y – Fault or Unbalance Loading N – No Fault)

I12 (kA)

I23 (kA)

I31 (kA)

IMax = max (I12, I23, I31)

IMax+ > τB (or) IMax > τi (Y – Fault, N–Unbalanced Loading)

V1+ (kV)

V2+ (kV)

V3+ (kV)

Min V+ (kV)

Faulty Bus Detected

θcp12 (rad)

θ cp23 (rad)

θ cp31 (rad)

Max θcp (rad)

Faulted Line Detected

 AB, Line 2–3, 120 km from Bus 2, FR = 10 Ω, FIA = 1080

33.29

62.72

64.33

Y

0.07

3.79

0.08

3.79

Y

353.75

280.56

265.00

265.00

Bus 3

0.00

3.35

0.07

3.35

Line 23

Fault Classification

 Fault Created

αi0 (A)

αi1 (A)

αi2 (A)

βi0 (deg)

βi1 (deg)

βi2 (deg)

γi01i0i1)

γi21i2i1)

δi21i2- βi1) (deg)

Is γi01 ≈ 1?

Is γi21 ≈ 1?

Fault type

Is δi01 ≈ 60?

Fault classified

 AB, Line 2–3, 120 km from Bus 2, FR = 10 Ω, FIA = 1080

0.078

3424.536

3722.221

56.282

43.566

102.827

0.00

1.087

59.261

N

Y

LL

Y

AB

Fault Location

 Fault Created

Va+ (kV)

Vb+ (kV)

Iab+ (A)

Iba+ (A)

Calculated distance (dcalculated)

Error (%)

AB, Line 2–3, 120 km from Bus 2, FR = 10 Ω, FIA = 1080

275.231–54.399i

261.035–45.679i

153.492–1585.769i

− 562.477 + 1803.866i

120.961

0.48