Table 2 Comparison between simulation and theoretical results for three-phase fault at f4

From: Modeling methodology and fault simulation of distribution networks integrated with inverter-based DG

Phasors

Simulation results

Theoretical results

Absolute errors

Relative errors/%

\( {\dot{I}}_{{\mathrm{L}}_2\mathrm{A}} \)

Amp.

1.515

1.512

0.003

0.200

Ang.

−78.4。

−82.8。

4.4。

2.458

\( {\dot{I}}_{{\mathrm{L}}_3\mathrm{A}} \)

Amp.

1.603

1.610

0.008

0.473

Ang.

−80.7。

−82.8。

2.1。

1.210

\( {\dot{I}}_{{\mathrm{L}}_4\mathrm{A}} \)

Amp.

1.838

1.758

0.080

4.354

Ang.

−82.4。

−87.3。

4.9。

2.689

\( {\dot{V}}_{MA} \)

Amp.

4.902

4.659

0.243

4.961

Ang.

−31.9。

−33.5。

1.6。

0.928

\( {\dot{V}}_{NA} \)

Amp.

2.051

1.891

0.160

7.803

Ang.

−33.1。

−36.1。

3.0。

1.675

  1. Notice: Relative error of angle is compared with 180。