Table 4 Setting values of outgoing line protection

From: Research on the protection coordination of permanent magnet synchronous generator based wind farms with low voltage ride through capability

Protection type

Section I

Section II

Section III

Zero-sequence protection

Setting(A)

1300

736

150

Time(s)

0

0.4

0.7

Distance protection

Setting(Ω)

15.193

32.735

56.1

Time(s)

0

0.4

1.6