Skip to main content

Table 4 Comparison of accuracy of different fault between T and Substation B

From: Experimental studies on impedance based fault location for long transmission lines

Fault Type

RFault

Location

Fault Location Error (%)

Ω

km

One-end Function Location

With the proposed shceme

AB

0

175

4.4888

0.3111

AB

0

200

4.5066

−0.089

AB

50

175

9.9644

0.8

AB

50

200

12.44

0.2667

ABG

0

175

2.24

0.5778

ABG

0

200

4.4044

0.2222

ABG

50

175

191.87

0.8

ABG

50

200

228.4

−0.089

BG

0

175

8.2133

0.7111

BG

0

200

8.7911

0.2222

BG

50

175

17.1289

0.4

BG

50

200

23.3778

0.4