Skip to main content

Table 3 Comparison of accuracy of different fault between S and T

From: Experimental studies on impedance based fault location for long transmission lines

Fault Type

RFault

Location

Fault Location Error (%)

Ω

km

With two ends method

Relay Fault Location Function

With the proposed shceme

AB

0

100

3.4222

5.1733

0.2222

AB

0

125

2.7111

4.8311

0.0444

AB

50

100

3.3333

4.9333

0.6667

AB

50

125

2.6222

4.6133

−0.089

ABG

0

100

3.3333

4.9333

0.6667

ABG

0

125

2.6222

4.6133

−0.089

ABG

50

100

3.2444

139.2133

0

ABG

50

125

2.5333

143.2489

−0.356

BG

0

100

3.1111

6.6488

0.6667

BG

0

125

2.2667

7.1155

−0.622

BG

50

100

2.8444

8.8933

0.3556

BG

50

125

2.1333

10.6889

0.3556