Skip to main content

Table 5 Simulation results of N3N4 in closed loop network model when internal faults occur at f7

From: A d-axis based current differential protection scheme for an active distribution network

Fault type

Rf /(Ω)

Sdiff /kA

Sres /kA

Result

Three-phase

0

246.146

34.430

Internal fault

Two-phase

0

152.949

21.421

Internal fault

Two-phase-ground

0

143.238

20.011

Internal fault

 

5

18.437

2.423

Internal fault

 

50

2.115

0.175

Internal fault