From: Pilot protection of hybrid MMC DC grid based on active detection
Sampling rates (kHz) | Correlation coefficient (positive/negative) | Fault section | Fault pole | Operate or not (Y/N) |
---|---|---|---|---|
2 | −0.833/0.905 | internal | positive | Y |
5 | −0.825/0.917 | internal | positive | Y |
10 | −0.819/0.913 | internal | positive | Y |
15 | −0.896/0.924 | internal | positive | Y |
20 | −0.931/0.911 | internal | positive | Y |