Table 4 Protection results with different sampling rates

From: Pilot protection of hybrid MMC DC grid based on active detection

Sampling rates (kHz)

Correlation coefficient (positive/negative)

Fault section

Fault pole

Operate or not (Y/N)

2

−0.833/0.905

internal

positive

Y

5

−0.825/0.917

internal

positive

Y

10

−0.819/0.913

internal

positive

Y

15

−0.896/0.924

internal

positive

Y

20

−0.931/0.911

internal

positive

Y

  1. From the simulation results, it can be seen that the correlation coefficient is largely not affected by the sampling rate, ensuring the correct operation of the protection in case of internal faults